- 230 VAC INPUT
- 28 VDC OUTPUT
- Safety in accordance with
DIN EN 62368-1 & DIN EN 54-4 - Wandmontage
- IP Rating: IP 30
- 2 x 12 VDC / 2.3 Ah rechargeable batteries can be integrated
- Integrated battery monitoring system
- Temperature-controlled charging voltage adjustment
- Integration into bus systems for fault transmission to the fire alarm control panel
Technical Specifications
Electrical Specifications
| INPUT | DCU 2401 R2 | ||
|---|---|---|---|
| Rated input voltage | 230 VAC (-15 % … +10 %) | ||
| Input voltage range | 195.5 … 253 VAC | ||
| Input current | 0.4 A | ||
| Frequency | 50 Hz ±5 % | ||
| OUTPUT | DCU 2401 R2 | ||
|---|---|---|---|
| Nominal output voltage when connected to the mains | 28.0 VDC ±5 % | ||
| Output current | 1.4 A | ||
| Nominal output power | 39.2 W | ||
| Output voltage when running on battery power | 19.5 … 28.4 VDC | ||
| ENERGY STORAGE | DCU 2401 R2 | ||
|---|---|---|---|
| Transitional period | at 1,4 A about 60 minutes | ||
| Charging current | typ. 200 mA | ||
| Deep discharge protection | typ. 20.0 VDC | ||
| Discharge warning contact | typ. 22.0 VDC | ||
| Storage type prepared for type: | VRLA-AGM; 2 x 12.0 VDC | ||
| Storage capacity | 2.1 … 2.3 Ah | ||
| SIGNALLING AND COMMUNICATION | DCU 2401 R2 | ||
|---|---|---|---|
| Signalling | internal LEDs and signal contacts | ||
| EFFICIENCY | DCU 2401 R2 | ||
|---|---|---|---|
| Efficiency typ. | 88 % | ||
| ELECTRICAL PROTECTION | DCU 2401 R2 | ||
|---|---|---|---|
| Internal battery fuse | T 5.0 A (FKS) | ||
| Internal output protection | T 2.5 A (5 x 20 mm) | ||
Mechanical Specifications
| DCU 2401 R2 | |||
|---|---|---|---|
| Width | 205 mm | ||
| Height | 218 mm | ||
| Depth | 88 mm | ||
| Weight | 1.1 kg (approx. 3.0 kg including battery) | ||
| Installation method | Wall mounting | ||
Connection Details
| CONNECTION 1 | DCU 2401 R2 | ||
|---|---|---|---|
| Connection type | Input | ||
| Connection technology | Screw-type / plug-in terminals | ||
| CONNECTION 2 | DCU 2401 R2 | ||
|---|---|---|---|
| Connection type | Output | ||
| Connection technology | Screw-type / plug-in terminals | ||
Protection and Safety
| PROTECTION AND SAFETY | DCU 2401 R2 | ||
|---|---|---|---|
| IP Rating | IP 30 | ||
| Protection class | I | ||
Environmental Conditions
| DCU 2401 R2 | |||
|---|---|---|---|
| Ambient temperature (operation) | -5 … +40 °C | ||
| Ambient temperature (storage) | -20 … +45 °C | ||
| Cooling | natural convection | ||
Standards and Regulations
| DCU 2401 R2 | |||
|---|---|---|---|
| EU Declaration of Conformity in accordance with | 2011/65/EU, 2014/35/EU, 2014/30/EU, (EU)305/2011 | ||
| Standards and Regulations | DIN EN IEC 61000-6-3 DIN EN IEC 61000-6-2 DIN EN 54-4 DIN EN IEC 62368-1 DIN VDE 0100-560 |
||
| Certificate number | 0560-CPR-212190022 | ||
Commercial Data
| DCU 2401 R2 | |||
|---|---|---|---|
| Product group | All-in-One UPS | ||
| Packaging unit | 1 item | ||
| Type of packaging | Cardboard box | ||
| Country of origin | DE | ||
| HS Code | 85044095 | ||
| Item number | 87701 | ||
Product Description
The DCU 2401 R2 is the successor model to the DCU 2401, with an identical design, and is therefore directly interchangeable. It ensures an uninterruptible power supply for alarm devices, signalling devices and linear fire detectors in accordance with EN 54-4 and complies with the safety standard DIN EN 62368-1. The input power supply, UPS and battery charging functions are integrated – as is a relay board that reports the status via potential-free contacts.
Approvals and Applications

CE Marking
2011/65/EU, 2014/35/EU, 2014/30/EU, (EU)305/2011
Konzept Energietechnik - DC USV Systeme und StromversorgungComplementary Products

SUN Battery SB12-2.3V0
AGM lead battery (OGiV-AGM) | 12 VDC | 2.3 Ah (C20) | T1 terminal (4.8 mm)